Quick start-up guide
23
Parameter setting examples
PROFIdrive communication profile with PPO Type 1
With the FPBA-01, data-consistent communication can be used,
meaning that the whole cyclic data frame is transmitted during a
single program cycle. Some PLCs handle this internally, but others
must be programmed to transmit data-consistent telegrams (for
more information, see the chapter Communication). For example,
Siemens Simatic S7 requires the use of special functions SFC15
and SFC14.
Drive parameter Example setting for ACS350
1001 EXT1 COMMANDS COMM
1103 REF1 SELECT COMM
1601 RUN ENABLE COMM
1604 FAULT RESET SEL COMM
9802 COMM PROT SEL EXT FBA
5101 FBA TYPE PROFIBUS DP*
5102 NODE ADDRESS 3
5103 BAUDRATE 12000*
5104 PPO TYPE 1 (= PPO1)*
5105 PROFILE 0 (= PROFIdrive)
• • •
5127 FBA PAR REFRESH REFRESH
*Read-only or automatically detected
Kommentare zu diesen Handbüchern