PROFIdrive parameters
112
929 R Unsigned16 Selected PPO type
Value PPO type Configuration
1 PPO1 F3h, F1h
2 PPO2 F3h, F5h
3PPO3F1h
4PPO4F5h
5 PPO5 F3h, F9h
6PPO6F9h
Note: This parameter is not available if
Standard telegram STD1 or STD20 are
selected.
930 R/W Unsigned16 Selection switch for communication profile.
Value Mode
1 PROFIdrive
8001h ABB Drives
8002h Transparent 16
8003h Transparent 32
933 R/W Unsigned16 Selection switch for Control word, bit 11.
Value Module Control word bit
0 None
1 to 5 Vendor specific 1 to 5*
* The meaning of vendor specific bits is
defined by drive application program.
934 R/W Unsigned16 Selection switch for Control word, bit 12.
(See parameter 933 for coding)
935 R/W Unsigned16 Selection switch for Control word, bit 13.
(See parameter 933 for coding)
936 R/W Unsigned16 Selection switch for Control word, bit 14.
(See parameter 933 for coding)
937 R/W Unsigned16 Selection switch for Control word, bit 15.
(See parameter 933 for coding)
Para-
meter
R/W
*
Data type Description