338 Parameter listing and descriptions
ACH550-01 User's Manual
HVAC
default Supply fan Return fan
Cooling
tower fan Condenser
Booster
pump
Parameter
name
Par.
index
123456
22 ACCEL/
ACC/DEC 1/2
SEL
2201 NOT SEL NOT SEL NOT SEL NOT SEL NOT SEL NOT SEL
DECEL
ACCELER
TIME 1
2202 30.0 s 15.0 s 15.0 s 30.0 s 10.0 s 5.0 s
DECELER
TIME 1
2203 30.0 s 15.0 s 15.0 s 30.0 s 10.0 s 5.0 s
RAMP SHAPE
1
2204 0.0 s 0.0 s 0.0 s 0.0 s 0.0 s 0.0 s
ACCELER
TIME 2
2205 60.0 s 60.0 s 60.0 s 60.0 s 60.0 s 60.0 s
DECELER
TIME 2
2206 60.0 s 60.0 s 60.0 s 60.0 s 60.0 s 60.0 s
RAMP SHAPE
2
2207 0.0 s 0.0 s 0.0 s 0.0 s 0.0 s 0.0 s
EMERG DEC
TIME
2208 1.0 s 1.0 s 1.0 s 1.0 s 1.0 s 1.0 s
RAMP INPUT
0
2209 NOT SEL NOT SEL NOT SEL NOT SEL NOT SEL NOT SEL
23 SPEED PROP GAIN 2301 5.00 5.00 5.00 5.00 5.00 5.00
CONTROL
INTEGRATION
TIME
2302 0.50 s 0.50 s 0.50 s 0.50 s 0.50 s 0.50 s
DERIVATION
TIME
2303 0 ms 0 ms 0 ms 0 ms 0 ms 0 ms
ACC
COMPEN-
SATION 2304 0.00 s 0.00 s 0.00 s 0.00 s 0.00 s 0.00 s
AUTOTUNE
RUN
2305 OFF OFF OFF OFF OFF OFF
25 CRITICAL
CRIT SPEED
SEL
2501 OFF OFF OFF OFF OFF OFF
SPEEDS
CRIT SPEED
1 LO
2502
0Hz /
0rpm
0Hz /
0rpm
0Hz /
0rpm
0Hz /
0rpm
0Hz /
0rpm
0Hz /
0rpm
CRIT SPEED
1 HI
2503
0Hz /
0rpm
0Hz /
0rpm
0Hz /
0rpm
0Hz /
0rpm
0Hz /
0rpm
0Hz /
0rpm
CRIT SPEED
2 LO
2504
0Hz /
0rpm
0Hz /
0rpm
0Hz /
0rpm
0Hz /
0rpm
0Hz /
0rpm
0Hz /
0rpm
CRIT SPEED
2 HI
2505
0Hz /
0rpm
0Hz /
0rpm
0Hz /
0rpm
0Hz /
0rpm
0Hz /
0rpm
0Hz /
0rpm
CRIT SPEED
3 LO
2506
0Hz /
0rpm
0Hz /
0rpm
0Hz /
0rpm
0Hz /
0rpm
0Hz /
0rpm
0Hz /
0rpm
CRIT SPEED
3 HI
2507
0Hz /
0rpm
0Hz /
0rpm
0Hz /
0rpm
0Hz /
0rpm
0Hz /
0rpm
0Hz /
0rpm
26 MOTOR
FLUX OPT
ENABLE
2601 ON ON ON ON ON ON
CONTROLS
FLUX
BRAKING
2602 OFF OFF OFF OFF OFF OFF
IR COMP
VOLT
26030 V0 V0 V0 V0 V0 V
IR COMP
FREQ
2604 80% 80% 80% 80% 80% 80%
U/F RATIO 2605 SQUARED SQUARED SQUARED SQUARED SQUARED SQUARED
SWITCHING
FREQ
2606 4 kHz 4 kHz 4 kHz 4 kHz 4 kHz 4 kHz
SWITCH
FREQ CTRL
2607 ON ON ON ON ON ON
SLIP COMP
RATIO
2608 0% 0% 0% 0% 0% 0%
NOISE
SMOOTHING
2609 DISABLE DISABLE DISABLE DISABLE DISABLE DISABLE
DC
STABILIZER
2619 DISABLE DISABLE DISABLE DISABLE DISABLE DISABLE