ABB RCNA-01 Bedienungsanleitung Seite 230

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 474
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 229
226 Parameter listing and descriptions
ACH550-01 User's Manual
2302 INTEGRATION TIME 0…600.00 s
Sets the integration time for the speed controller.
The integration time defines the rate at which the controller output
changes for a constant error value.
Shorter integration times correct continuous errors faster.
Control becomes unstable if the integration time is too short.
The figure shows the speed controller output after an error step (error
remains constant).
Note: You can use parameter 2305
AUTOTUNE RUN to automatically set
the integration time.
Code Description Range
T
I
Controller output
%
K
p
· e
K
p
· e
e = Error value
K
p
= Gain = 1
T
I
= Integration time > 0
T
D
= Derivation time = 0
t
Seitenansicht 229
1 2 ... 225 226 227 228 229 230 231 232 233 234 235 ... 473 474

Kommentare zu diesen Handbüchern

Keine Kommentare