204 Parameter listing and descriptions
ACH550-01 User's Manual
1603 PASS CODE 0…65535
Entering the correct pass code allows you to change the parameter
lock.
See parameter 1602 above.
Code 358 allows you to change the value of parameter 1602 once.
This entry reverts back to 0 automatically.
1604 FAULT RESET SEL -6…8
Selects the source for the fault reset signal. The signal resets the drive
after a fault trip if the cause of the fault no longer exists.
0 =
KEYPAD – Defines the control panel as the only fault reset source.
• Fault reset is always possible with control panel.
1 =
DI1 – Defines digital input DI1 as a fault reset source.
• Activating the digital input resets the drive.
2…6 =
DI2…DI6 – Defines digital input DI2…DI6 as a fault reset source.
•See
DI1 above.
7 =
START/STOP – Defines the Stop command as a fault reset source.
• Do not use this option when fielbus communication provides the
start, stop and direction commands.
8 =
COMM – Defines the fieldbus as a fault reset source.
• The Command Word is supplied through fieldbus communication.
• The bit 4 of Command Word 1 (parameter 0301) resets the drive.
-1 =
DI1(INV) – Defines an inverted digital input DI1 as a fault reset
source.
• De-activating the digital input resets the drive.
-2…-6 =
DI2(INV)…DI6(INV) – Defines an inverted digital input DI2…DI6
as a fault reset source.
•See
DI1(INV) above.
Code Description Range