138 Serial communications
ACH550-01 User's Manual
Changes made to EFB communication parameters (group 53)
do not take effect until you perform one of the following:
Cycle the drive power OFF and ON, or
Set parameter 5302 to 0, and then back to a unique EFB
station ID.
Protocol selection
EFB communication parameters
5 Continue the guided set-up
with the assistant.
Code Description Range
9802 COMM PROT SEL 0…5
Selects the communication protocol.
0 =
NOT SEL – No communication protocol selected.
1 =
STD MODBUS – The drive communicates via a Modbus controller via
the RS485 serial link (X1 communications, terminal).
• See also parameter Group 53: EFB PROTOCOL.
2 =
N2 – The drive communicates via an N2 controller via the RS485
serial link (X1 communications, terminal).
• See also parameter Group 53: EFB PROTOCOL.
3 = FLN – The drive communicates via an FLN controller via the RS485
serial link (X1 communications, terminal).
• See also parameter Group 53: EFB PROTOCOL.
5 =
BACNET – The drive communicates via a BACnet controller via the
RS485 serial link (X1 communications, terminal).
• See also parameter Group 53: EFB PROTOCOL.
Code Description Range
5301 EFB PROTOCOL ID 0…0xFFFF
Contains the identification and program revision of the protocol.
Format: XXYY, where xx = protocol ID, and YY = program revision.
5302 EFB STATION ID 0…65535
Defines the node address of the RS485 link.
The node address on each unit must be unique.
5302 EFB STATION ID
PAR EDIT
128
OFF
EXIT SAVE
00:00