152 Serial communications
ACH550-01 User's Manual
1606 LOCAL LOCK -6…8
Defines control for the use of the HAND mode. The HAND mode allows
drive control from the control panel (operator keypad).
•When
LOCAL LOCK is active, the control panel cannot change from
the AUTO mode to the HAND mode.
8 =
COMM – Defines bit 14 of Command Word 1 (parameter 0301) as the
control for setting the local lock.
• The Command Word is supplied through fieldbus communication.
1607 PARAM SAVE 0=DONE, 1=SAVE
Saves all altered parameters to the permanent memory.
Parameters altered through a fieldbus are not automatically saved to
the permanent memory. To save, you must use this parameter.
If 1602
PARAMETER LOCK = 2 (NOT SAVED), parameters altered from
the control panel (operator keypad) are not saved. To save, you must
use this parameter.
If 1602
PARAMETER LOCK = 1 (OPEN), parameters altered from the
control panel are stored immediately to permanent memory.
0 =
DONE – The value changes automatically when all parameters are
saved.
1 =
SAVE… – Saves altered parameters to the permanent memory.
1608 START ENABLE 1 -6…7
Selects the source of the Start enable 1 signal. See the figure on page
208.
Note: Start enable functionality differs from the Run enable
functionality.
7 =
COMM – Assigns the fieldbus Command Word as the source for the
Start enable 1 signal.
• Bit 2 of Command Word 2 (parameter 0302) activates the Start
disable 1 signal.
• See the fieldbus users manual for detailed instructions.
1609 START ENABLE 2 -6…7
Selects the source of the Start enable 2 signal.
Note: Start enable functionality differs from the Run enable
functionality.
7 =
COMM – Assigns the fieldbus Command Word as the source for the
Start enable 2 signal.
• Bit 3 of Command Word 2 (parameter 0302) activates the Start
disable 2 signal.
• See the fieldbus users manual for detailed instructions.
Code Setting for fieldbus control & description Range
Seitenansicht 155
1 2 ... 151 152 153 154 155 156 157 158 159 160 161 ... 473 474