278 Parameter listing and descriptions
ACH550-01 User's Manual
4016 ACT1 INPUT 1…7
Defines the source for actual value 1 (
ACT1). See also parameter 4018
ACT1 MINIMUM.
1 =
AI1 – Uses analogue input 1 for ACT1.
2 =
AI2 – Uses analogue input 2 for ACT1.
3 =
CURRENT – Uses current for ACT1.
4 =
TORQUE – Uses torque for ACT1.
5 =
POWER – Uses power for ACT1.
6=
COMM ACT 1 – Uses value of signal 0158 PID COMM VALUE 1 for ACT1.
7=
COMM ACT 2 – Uses value of signal 0159 PID COMM VALUE 2 for ACT1.
4017 ACT2 INPUT 1…7
Defines the source for actual value 2 (
ACT2). See also parameter 4020
ACT2 MINIMUM.
1 =
AI1 – Uses analogue input 1 for ACT2.
2 =
AI2 – Uses analogue input 2 for ACT2.
3 =
CURRENT – Uses current for ACT2.
4 =
TORQUE – Uses torque for ACT2.
5 =
POWER – Uses power for ACT2.
6=
COMM ACT 1 – Uses value of signal 0158 PID COMM VALUE 1 for ACT2.
7=
COMM ACT 2 – Uses value of signal 0159 PID COMM VALUE 2 for ACT2.