Parameter listing and descriptions 167
ACH550-01 User's Manual
0113 CTRL LOCATION 0=HAND, 1=EXT1,
2=EXT2
Active control location. Alternatives are:
0 =
HAND
1 = EXT1
2 =
EXT2
0114 RUN TIME (R) 0…9999 h
Drive’s accumulated running time in hours (h)
•Can be reset by pressing the UP and DOWN keys simultaneously
when in the Parameters mode.
0115 KWH COUNTER (R) 0…65535 kWh
Drive’s accumulated power consumption in kilowatt hours
The counter value is accumulated till it reaches 65535 after which the
counter rolls over and starts again from 0.
The counter can be reset by pressing the UP and DOWN keys
simultaneously when in the Parameters mode.
0116 APPL BLK OUTPUT 0…100%
(0…600% for torque)
Application block output signal. Value is from either:
PFA control, if PFA Control is active, or
parameter 0112
EXTERNAL REF 2.
0118 DI 1-3 STATUS 000…111 (0…7 decimal)
Status of the three digital inputs
Status is displayed as a binary number.
1 indicates that the input is activated.
0 indicates that the input is deactivated.
0119 DI 4-6 STATUS 000…111 (0…7 decimal)
Status of the three digital inputs
See parameter 0118
DI
1-3
STATUS
.
0120 AI 1 0…100%
Relative value of analogue input 1 in %
0121 AI 2 0…100%
Relative value of analogue input 2 in %
Code Description Range
DI1 DI2 DI3
Seitenansicht 170