Derating
The load capacity (current and power) decreases if the
installation site altitude exceeds 1000 meters (3300 ft), or if the
ambient temperature exceeds 40°C (104°F) or if 8 kHz switching
frequency (parameter 2206) is used.
Temperature derating
In the temperature range +40°C...50°C (+104°F...122°F) the
rated output current is decreased 1% for every 1°C (1.8°F)
above 40°C (+104°F). The output current is calculated by
multiplying the current given in the rating table by the derating
factor.
Example. If the ambient temperature is 50°C (+122°F) the
derating factor is 100% - 1%/°C = 90% or 0.90.
The output current is then 0.90*I
2N
.
Altitude derating
In altitudes from 1000...4000 m (3300...13,200 ft) above sea
level, the derating is 1% for every 100 m (330 ft). If the
installation site is higher than 2000 m (6600 ft) above sea level,
please contact your local ABB distributor or office for further
information.
Single phase supply derating
For 208...240 Volt series drives, a single phase supply can be
used. In that case, the derating is 50%.
Switching frequency derating
If the 8 kHz switching frequency (parameter 2206) is used,
derate P
N
and I
2N
to 80%.