ACH550 User's Manual
Wiring and applications 105
Floating point
1
SCR
Signal cable shield (screen)
2
AI1
Not used
3
AGND
Analog input circuit common
410 V
Reference voltage 10 VDC
5
AI2
Not used
6
AGND
Analog input circuit common
7
AO1
Output frequency: 0(4)...20 mA
8
AO2
Output current: 0(4)...20 mA
9
AGND
Analog output circuit common
10 24 V
11 GND
Auxiliary voltage output + 24 V
Common for DI return signals
12
DCOM
Digital input common for all
13
DI1
Start/Stop: Activation starts the drive
14
DI2
Run enable: Deactivation stops the drive**
15
DI3
Constant Speed 1: (Par 1202)*
16
DI4
Start enable 1:Deactivation stops the drive**
17
DI5
Reference up: Activation increases the reference
18 DI6
Reference down: Activation decreases the reference
19
RO1C
Relay output 1 (Par 1401)
20
RO1A
Default operation
21
RO1B
Started=> 19 connected to 21
22
RO2C
Relay output 2 (Par 1402)
23 RO2A
Default operation
24
RO2B
Running=> 22 connected to 24
25
RO3C
Relay output 3 (Par 1403)
26
RO3A
Default operation
27
RO3B
Fault (-1)=> 25 connected to 27
*Not available if PID is active
**Disable/enable with parameters 1601 and 1608
Note! Drive starts only if possible protection functions (Run enable or Start enable 1 and 2)
are activated from I/O or disabled with parameters.