196 Parameter listing and descriptions
ACH550 User's Manual
1209 TIMED MODE SEL 1...2
Defines timer activated, constant speed mode. Timer can be used to
change between external reference and a maximum of three constant
speeds or to change between a maximum of 4 selectable speeds, i.e.
constant speeds 1,2,3 and 4.
1 =
EXT/CS1/2/3 - Selects an external speed when no timer is active,
selects Constant speed 1 when Timer 1 is active, Selects Constant
speed 2 when Timer 2 is active and selects Constant speed 3 when
both Timers 1 and 2 are active.
2 =
CS1/2/3/4 - Selects Constant speed 1 when no timer is active,
selects Constant speed 2 when Timer 1 is active, selects Constant
speed 3 when Timer 2 is active, selects Constant speed 4 when both
timers are active.
Code Description Range
TIMER1 TIMER2 Function
0 0 External reference
1 0 Constant speed 1(1202)
0 1 Constant speed 2 (1203)
1 1 Constant speed 3 (1204)
TIMER1 TIMER2 Function
0 0 Constant speed 1 (1202)
1 0 Constant speed 2 (1203)
0 1 Constant speed 3 (1204)
1 1 Constant speed 4 (1205)