ABB ACH550 Bedienungsanleitung Seite 165

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 435
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 164
Serial communications 161
ACH550 User's Manual
The Actual Speed is scaled as follows:
Fault handling
The ACH550 indicates all faults in clear text and fault number in
the control panel display. Refer to the User’s Manual.
Additionally a fault code is allocated to each fault name shown in
parameters 401, 412 and 413. The fieldbus specific fault code is
indicated as a hexadecimal value coded according to the
DRIVECOM specification. Note that not all fieldbusses support
the fault code indication. The table below defines the fault codes
for each fault name.
Actual
value
Range Reference type Scaling
SPEED Fieldbus
specific
Speed -100% = -[par. 9908]
0 = 0
+100 = [par. 9908]
Frequency -100% = -[par. 9907]
0 = 0
+100 = [par. 9907]
Fault name in control panel Drive
fault code
Fieldbus fault code
OVERCURRENT 1 2310h
DC OVERVOLT 2 3210h
DEV OVERTEMP 3 4210h
SHORT CIRC 4 2340h
OVERLOAD 5 FF6Bh
DC UNDERVOLT 6 3220h
AI1 LOSS 7 8110h
AI2 LOSS 8 8110h
MOT OVERTEMP 9 4310h
PANEL LOSS 10 5300h
ID RUN FAIL 11 FF84h
MOTOR STALL 12 7121h
EXT FAULT 1 14 9000h
EXT FAULT 2 15 9001h
00Template.book Page 161 Friday, January 2, 2004 2:55 PM