Quick start-up guide
22
Example Configuration: ABB Drives Profile w/ Speed and Torque
on ACS350
1 The ABB Drives Profile does provide a means to supply a RUN
ENABLE signal via DeviceNet. The RUN ENABLE for the drive
may be set to COMM or another source (e.g. a digital input).
2 These parameters are ignored when using ABB Drives Profile.
3 OUTPUT NUM PARS and INPUT NUM PARS should always be
set to 10, except as provided for in the Appendix.
Drive parameter Example setting for ACS350
11.01 EXT1 COMMANDS COMM
11.03 REF1 SELECT COMM
16.01 RUN ENABLE COMM
1
16.04 FAULT RESET SEL COMM
98.02 COMM PROT SEL EXT FBA
51.01 FBA TYPE DEVICENET
51.02 MAC ID 53
51.03 BAUD RATE 2 (= 500kbit/s)
51.04 RESERVED 0
51.05 ODVA STOP FUNC 0 (= Ramp Stop)
2
51.06 OUTPUT INSTANCE 802 (=ABB Drives Profile
w/ Set Speed and Set Torque)
51.07 OUTPUT NUM PARS 10
3
51.08 INPUT INSTANCE 852 (=ABB Drives Profile
w/ Set Speed and Set Torque)
51.09 INPUT NUM PARS 10
3
51.10 ODVA SPEED SCALE 128 (= 1 RPM)
2
51.11 ODVA TORQUE SCALE 128 (= 1 Nm)
2
51.27 FBA PAR REFRESH REFRESH