ELECTRICAL CONNECTIONS
The bus powers the transmitter; thus, power and
fieldbus signals share the same pair of wires.
Separate conduit for power and sensor wiring is
encouraged. Prior to entering the instrument housing,
terminate rigid conduit and install a short length of
flexible conduit to reduce stress to the housing.
Signal wiring must not come in close proximity to
high-power equipment or to cabling from such
equipment. Wiring must be in accordance to the
applicable local codes and fieldbus requirements (see
Supplementary Documentation). Bus cabling must
conform to IEC 61158-2.
The terminal blocks located in the rear of the
transmitter accept wire sizes from 12 to 24 AWG.
Pin-style terminals should be used for all connections.
The terminal block label identifies all electrical
connections and should be followed when wiring the
transmitter. Observance to polarity is not required;
however, polarity indications have been provided for
consistence. Voltage requirements are listed in the
Specifications and must be observed. Ensure the
power supply that provides bus power is complaint
with IEC 61158-2.
Normal grounding practice is to terminate all grounds
in the control room side, in which case the field side of
the screen should be adequately protected to avoid
contact with metallic objects. For bus-powered
systems, the grounding of the shield should be close
to the power supply unit. For IS systems, the
grounding should be at the safety barrier earth
connection. The transmitter case should be grounded.
Ground connections are provided internally (in the
terminal compartment) and externally.
REAR VIEW
POWER/OUTPUT
CONNECTIONS
TB2
TB1
4
3
2
1
SIGNAL
DRIVE1
2
SENSE
3
SENSE
4DRIVE
5
RTD
RTD6
SHIELD
8
7
INTERNAL GROUND
TERMINALS
EXTERNAL
GROUND
TERMINAL
SENSOR CABLE TO
BE SEALED IN CONDUIT
VOLTAGE AT POWER
TERMINALS TB1-1
AND TB1-2 MUST BE
BETWEEN 9 AND 32 VDC.
CABLING TO CONFORM
WITH IEC 61158-2.
FIELDBUS
Green
Red
Black
Blue
White
Yellow
TERMINAL
COLOR
CODE
FUNCTION
TB2-1
TB2-2
TB2-3
TB2-4
TB2-5
TB2-6
TB2-7
TB2-8
Drive
Sense
Sense
RTD
RTD
SHIELD
FOR
82EC
ONLY
FOR
82EC
ONLY
Figure 9 – Sensor and Power Wiring
Warning.
Use this equipment only in those classes of
hazardous locations listed on the nameplate.
Uses in other hazardous locations can lead to
unsafe conditions that can injure personnel and
damage equipment.