Fault tracing
92
Troubleshooting guide
Problem: ABB IP Configuration Tool does not find any SREA-01 units
Some firewall applications block the ABB IP Configuration Tool. If you are
experiencing problems with finding the SREA-01 unit, try disabling your firewall.
Make sure that SREA-01 is connected to the same network as the PC without any
gateways.
Try using a crossover Ethernet cable and connecting the PC to SREA-01 directly.
Problem: SREA-01 can not be connected to locally
Check that the link LED of the SREA-01 unit is lit. If necessary, check the
Ethernet cabling. Use a straight Ethernet cable when using a switch and a
crossover Ethernet cable when connecting directly to a PC.
Make sure that SREA-01 is configured with correct network settings. Try
connecting to it with a crossover Ethernet cable and make sure that your network
adapter is configured to the same subnet as the SREA-01 unit. Check that the
unit can be found by ABB IP Configuration Tool.
If you are using DHCP, make sure that the IP address of SREA-01 has not
changed automatically.
Make sure that your browser is not configured to use a proxy server for local
network connections.
Problem: SREA-01 can not be connected to from a remote location
Make sure that your internet service provider or network system does not block
port 80 from outside. If necessary, configure the SREA-01 to use an alternate web
server port (see section Webserver on page 75) and your firewall to allow traffic to
that port.
If you are using DHCP, make sure that the IP address of SREA-01 has not
changed automatically.
Problem: Logging in fails
Make sure that caps lock is turned off.
Make sure that JavaScript is enabled in your browser.
Try using Internet Explorer 6 or newer or Mozilla Firefox.
Problem: The drives are not found by SREA-01 or appear as ‘disconnected’
Check that you have selected the correct physical interface, baud rate and parity
on the Setup – Modbus page. Check that all drives are configured to use the
same baud rate and parity.
Check the Status page to see if communication works partially or not at all. Check
cabling, terminating resistors and the correct wiring of A/B channels or RX/TX
signals, depending on your setup.
Check that all drives have different node addresses.