Installation of the drive connection
36
Connecting to ACS/ACH550
When using ACS/ACH550, SREA-01 can be connected by using the following
interfaces:
Panel port of ACS/ACH550 (RS-232),
Embedded Modbus connector of ACS/ACH550 (RS-485),
RETA-01 Ethernet Adapter (Modbus TCP),
RETA-02 Ethernet Adapter (Modbus TCP).
The usual scenarios are described below:
Only a single drive, not controlled through SREA-01 or by other fieldbus
Connect SREA-01 directly to the panel port by using the supplied cable and
connector X1/RS-232. If you want to use the panel simultaneously, you can also use
the Embedded Modbus of the drive and RS-485.
Only a single drive, controlled by other fieldbus such as PROFIBUS
Connect SREA-01 directly to the panel port by using the supplied cable and
connector X1/RS-232.
When other fieldbus control such as PROFIBUS is required, the Embedded Modbus
interface of the drive can not be used.
Only a single drive, controlled by a Modbus TCP client that connects to SREA-01
Connect SREA-01 to the Embedded Fieldbus of the drive by using RS-485, because
the panel port can not be used to feed the control word to the drive.
Multiple drives, not controlled by another fieldbus such as PROFIBUS
Connect SREA-01 to the Embedded Fieldbus of the drive by using RS-485. This
way the drives can also be controlled by Modbus TCP clients that connect to
SREA-01.
Multiple drives, fieldbus control such as PROFIBUS required
Connect RS-232/RS-485 converters to the panel ports of the drives and connect the
RS-485 Modbus network to the RS-485 interface of SREA-01.
When other fieldbus control such as PROFIBUS is required, the Embedded Modbus
interface of the drive can not be used.
The drive is equipped with the RETA-01 or RETA-02 Ethernet Adapter
Connect SREA-01 to the same network with RETA-01 or RETA-02 and configure
both modules to use Modbus TCP for communication.