Installation of the drive connection
37
Note: If you are connecting by using the panel port, check the group 52 Panel
communication. If you are using the Embedded Modbus interface, check the group
53 EFB Protocol. Make sure that each drive has unique station ID and that the baud
rate and parity selections are the same for all drives and the SREA-01.
Note: When using RETA-01 or RETA-02, it must be configured to use Modbus TCP.
It can not be used to access the drive data if, for instance, Ethernet/IP is required in
the application.
Connecting to ACS800
When using ACS800, SREA-01 can be connected by using one of the following
drive option modules:
RMBA-01 Modbus Adapter (RS-485),
RETA-01 Ethernet Adapter (Modbus TCP),
RETA-02 Ethernet Adapter (Modbus TCP).
Please note that you can connect RMBA-01 to the slot 2 of the ACS800 even though
there is another fieldbus module such as RPBA-01 Profibus Adapter connected to
the slot 1.
Note: Check the settings in group 52 STANDARD MODBUS. Make sure that each
drive has unique station number (52.01) and that the baud rate and parity selections
(52.02, 52.03) are the same for all drives and the SREA-01.
Note: When using RETA-01, it must be configured to use Modbus TCP. It can not be
used to access the drive data if, for instance, Ethernet/IP is required in the
application.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]