30 CURRENT LIM Sets the output current limit of the drive. 2003
31 ACCEL TIME 1 Sets the acceleration time for Ramp 1. 2202
32 DECEL TIME 1 Sets the deceleration time for Ramp 1. 2203
33 HANDAUTO
ACT
Indicates whether the drive is in Hand or Auto control
(1 = HAND, 0 = AUTO).
34 ENA.DIS ACT Indicates the status of the Run Enable command, regardless
of its source (1 = ENABLE, 0 = DISABL).
35 ENA.DIS CMD Commanded by FLN to assert the Run Enable command
(1 = ENABLE, 0 = DISABL).
Parameter 1601 must be set to COMM for FLN to have this
control.
36 FLN LOC ACT Indicates if the drive has been placed in “FLN LOCAL” mode
by commanding either point 68 (FLN LOC CTL) or point 69
(FLN LOC REF). Commanding either of these points to FLN
(1) “steals” control from its normal source and places in under
FLN control.
Note that the HAND mode of the panel has priority over FLN
local control.
37 FLN CTL SRC Indicates if FLN is a source for control inputs
(1 = YES, 0 = NO).
Note that this status point is true if any of the following control
inputs are from FLN: Run/Stop, Ext1/2 Select or Run Enable.
38 FLN REF1 SRC Indicates if FLN is the source for speed reference 1
(1 = YES, 0 = NO).
39 FLN REF2 SRC Indicates if FLN is the source for speed reference 2
(1 = YES, 0 = NO).
40 RO1 COMMAND Controls the output state of Relay 1.
Parameter 1401 must be set to COMM for FLN to have this
control (1 = ON, 0 = OFF).
0134, bit 0
41 RO2 COMMAND Controls the output state of Relay 2.
Parameter 1402 must be set to COMM for FLN to have this
control (1 = ON, 0 = OFF).
0134, bit 1
42 RO3 COMMAND Controls the output state of Relay 3.
Parameter 1403 must be set to COMM for FLN to have this
control (1 = ON, 0 = OFF).
0134, bit 2
43 RO4 COMMAND Controls the output state of Relay 4. Access to relay 4 require
ACH550 option OREL.
Parameter 1410 must be set to COMM for FLN to have this
control (1 = ON, 0 = OFF).
0134, bit 3
44 RO5 COMMAND Controls the output state of Relay 5. Access to relay 5 require
ACH550 option OREL.
Parameter 1411 must be set to COMM for FLN to have this
control (1 = ON, 0 = OFF).
0134, bit 4
45 RO6 COMMAND Controls the output state of Relay 6. Access to relay 6 require
ACH550 option OREL.
Parameter 1412 must be set to COMM for FLN to have this
control (1 = ON, 0 = OFF).
0134, bit 5
FLN Detailed Point Descriptions