ABB RDNA-01 Bedienungsanleitung Seite 126

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 348
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 125
1-122 ACH550-UH User’s Manual
Parameters
2205 ACCELER TIME 2 0.0…1800.0 s 0.1 s 60.0 s
Sets the acceleration time for zero to maximum frequency for ramp pair 2.
See 2202
ACCELER TIME 1.
Used also as jogging acceleration time. See 1004
JOGGING SEL.
2206 DECELER TIME 2 0.0…1800.0 s 0.1 s 60.0 s
Sets the deceleration time for maximum frequency to zero for ramp pair 2.
See 2203
DECELER TIME 1.
Used also as jogging deceleration time. See 1004
JOGGING SEL.
2207 RAMP SHAPE 2 0.0…1000.0 s 0.1 s 0.0 s
Selects the shape of the acceleration/deceleration ramp for ramp pair 2.
See 2204
RAMP SHAPE 1.
2208 EMERG DEC TIME 0.0…1800.0 s 0.1 s 1.0 s
Sets the deceleration time for maximum frequency to zero for an emergency.
See parameter 2109
EMERG STOP SEL.
Ramp is linear.
2209 RAMP INPUT 0 -6…7 1 0 (
NOT SEL)
Defines control for forcing the speed to 0 with the currently used deceleration ramp (see parameters 2203
DECELER
TIME 1 and 2206 DECELER TIME 2).
0 =
NOT SEL – Not selected.
1 =
DI1 – Defines digital input DI1 as the control for forcing the speed to 0.
• Activating the digital input forces the speed to zero, after which the speed will stay at 0.
• De-activating the digital input: speed control resumes normal operation.
2…6 =
DI2…DI6 – Defines digital input DI2…DI6 as the control for forcing the speed to 0.
•See DI1 above.
7 =
COMM – Defines bit 13 of the Command Word 1 as the control for forcing the speed to 0.
• The Command Word is supplied through fieldbus communication.
• The Command Word is parameter 0301.
-1 =
DI1(INV) – Defines inverted digital input DI1 as the control for forcing the speed to 0.
• De-activating the digital input forces the speed to 0.
• Activating the digital input: speed control resumes normal operation.
-2…-6 =
DI2(INV)…DI6(INV) – Defines an inverted digital input DI2…DI6 as the control for forcing the speed to 0.
•See
DI1(INV) above.
Group 22: Accel/Decel
Code Description Range Resolution Default S
Seitenansicht 125