ABB FPBA-01 Spezifikationen Seite 8

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 21
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 7
8
Product series
1
Feature / frame size A B C D E0 E G
Current & Power
Nominal current (400 V) 3 to 8 A 10.5 to 18 A 25 to 50 A 61 to 94 A 103 to 144 A 166 to 210 A 430 to 720 A
Maximum current (400 V) 4.4 to 10.5 A 13.5 to 21 A 33 to 66 A 78 to 124 A 131 to 170 A 202 to 348 A 588 to 1017 A
Typical motor power (400 V) 1.1 to 3 kW 4 to 7.5 kW 9 to 22 kW 30 to 45 kW 55 to 75 kW 90 to 160 kW 200 to 400 kW
Braking chopper
Braking resistor
Input choke
EMC lter / C3 *
EMC lter / C2
Mounting and cooling
Air cooling
Side-by-side mounting
DIN-rail mounting
Removable power connectors
Removable control connectors
= standard = option, internal = option, external – = not available * External EMC lters are plug-in type lters that t to the drive within its installation footprint.
Ratings (U
N
= 480V)
Type Code Frame
Size
Input RMS Current Nominal Ratings Light Duty Heavy Duty Noise
level
Air
Flow
@ 60 Hz
I
1N
*I
1N
continuous
current
I
2N
rated
power
P
2N
maximum
current
I
MAX
continuous
current
I
LD
rated
power
P
LD
continuous
current
IHD
rated
power
PHD
A A A HP A Adc HP Adc HP dBA ft3/min
ACS850-04--03A0-5 A 2.3 4 3 1.5 4.4 2.8 1 2.5 1 47 10
ACS850-04--03A6-5 A 3.1 6 3.6 2 5.3 3.4 2 3 1.5 47 10
ACS850-04--04A8-5 A 4 7 4.8 3 7 4.5 2 4 2 47 10
ACS850-04--06A0-5 A 5.5 9 6 3 8.8 5.5 3 5 3 47 10
ACS850-04--08A0-5 A 6.6 11 8 5 10.5 7.6 5 6 3 47 10
ACS850-04--010A-5 B 8.7 13 10.5 5 13.5 9.7 5 9 5 39 30
ACS850-04--014A-5 B 12 18 14 7.5 16.5 13 7.5 11 7.5 39 30
ACS850-04--018A-5 B 16 23 18 10 21 16.8 10 14 10 39 30
ACS850-04--025A-5 C 20 25 15 33 23 15 19 10 63 80
ACS850-04--030A-5 C 26 30 20 36 28 20 24 15 63 80
ACS850-04--035A-5 C 30 35 25 44 32 20 29 20 71 120
ACS850-04--044A-5 C 36 44 30 53 41 30 35 25 71 120
ACS850-04--050A-5 C 42 50 30 66 46 30 44 30 71 120
ACS850-04--061A-5 D 55 61 40 78 57 40 52 40 70 170
ACS850-04--078A-5 D 65 78 60 100 74 50 69 50 70 170
ACS850-04--094A-5 D 82 94 60 124 90 60 75 50 70 170
ACS850-04-103A-5 E0 100 103 75 138 100 75 88 60 65 100
ACS850-04-144A-5 E0 142 144 100 170 141 100 100 75 65 240
ACS850-04-166A-5 E 163 166 125 202 155 125 115 75 65 240
ACS850-04-202A-5 E 198 202 150 282 184 150 141 100 65 240
ACS850-04-225A-5 E 221 225 150 326 220 150 163 125 65 240
ACS850-04-260A-5 E 254 260 200 326 254 200 215 150 65 240
ACS850-04-290A-5 E 283 290 200 348 286 200 232 150 65 240
ACS850-04--430A-5 G 423 430 350 588 425 350 340 250 72 720
ACS850-04--521A-5 G 501 521 450 588 516 450 370 300 72 720
ACS850-04--602A-5 G 581 602 500 840 590 500 477 400 72 720
ACS850-04--693A-5 G 674 693 550 1017 679 550
590 1) 500 72 720
ACS850-04--720A-5 G 705 720 600 1017 704 600 635 2) 500 72 720
Types, ratings and dimensions
Nominal ratings:
I
2N
: rated current available continuously without overloading at 40 °C.
I
max
: maximum output current. Available for 10 s at start, otherwise as long as
allowed by drive temperature. Note: max. motor shaft power is 150% P
hd
.
Typical ratings:
No-overload use
P
N
: typical motor power in no-overload use.
Light-duty use
I
Ld
: continuous current allowing 110% I
Ld
for 1min / 5 min at 40 °C.
P
Ld
: typical motor power in light-duty use.
Heavy-duty use
I
hd
: continuous current allowing 150% I
hd
for 1min / 5 min at 40 °C.
P
hd
: typical motor power in heavy-duty use.
The current ratings are the same regardless of the supply voltage within one
voltage range.
The ratings apply at 40 °C ambient temperature.
Frame
size
Height
3)
Depth
4)
Width Weight
in mm in mm in mm lb kg
A 14.3 364 7.8 197 3.7 93 7 3
B 15.0 380 10.8 274 4.0 101 11 5
C 22.3 567 10.9 276 6.5 166 35 16
D 22.3 567 10.9 276 8.7 221 51 23
E0 23.7 602 13.9 354 10.9 276 77 35
E 27.6 700 17.4 443 12.3 312 147 67
G
6
61.6 1564 22.4 568 22.1 562 441 205
Notes
All dimensions and weights are without options.
3) Height is the maximum measure without clamping plates.
4) An additional 50 mm should be reserved for feedback cabling if
FEN-01, 11 or 21 option is used.
5) Control panel adds 0.9in (23mm) to the depth
6) Frame G drives include separately mounted control section, 12.8h x 4.5d x 3.7w, 3 lb.
Dimensions
1) For ambient temperature of less than 95 deg. F (35 C), maximum overload is 150% of IHD. For ambient temperature of 104 deg. F (40 C), maximum overload is 145% of IHD.
2) For ambient temperature of less than 86 deg. F (30 C), maximum overload is 150% of IHD. For ambient temperature of 104 deg. F (40 C), maximum overload is 140% of IHD.
Seitenansicht 7
1 2 3 4 5 6 7 8 9 10 11 12 13 ... 20 21

Kommentare zu diesen Handbüchern