288 ACS550-01/U1 User’s Manual
Technical data
Effective motor cable shields
The general rule for cable shield effectiveness is: the better and tighter the cable’s
shield, the lower the radiated emission level. The following figure shows an example
of an effective construction (for example Ölflex-Servo-FD 780 CP, Lappkabel or
MCCMK, NK Cables).
EN 61800-3 compliant motor cables
The most efficient EMC filtering can be achieved by following these rules:
Motor cables must have an effective shield as described in section Effective
motor cable shields on page 288.
Motor cable shield wires must be twisted together into a bundle (pig-tail) – the
bundle length must be less than five times its width – and connected to the
terminal marked (at the bottom right-hand corner of the drive).
At the motor end, the motor cable shield must be earthed 360 degrees with an
EMC cable gland, or the shield wires must be twisted together into a bundle (pig-
tail) not longer than five times its width and connected to the PE terminal of the
motor.
See section Motor cable length for 400 V drives, columns “EMC limits” on page
284 to check the maximum motor cable lengths and the need for filters for 400 V
drives for IEC/EN 61800-3 compliance.
WARNING! Do not use RFI/EMC filters on IT systems.
Insulation jacket
Braided metallic shield
Inner insulator
L1
L2
L3