ACS550-01/U1 User’s Manual 187
Parameters
8104 REFERENCE STEP 2
Sets a percentage value that is added to the process reference.
Applies only when at least two auxiliary (constant speed) motors are running.
See parameter 8103
REFERENCE STEP 1.
8105 REFERENCE STEP 3
Sets a percentage value that is added to the process reference.
Applies only when at least three
auxiliary (constant speed) motors are running.
See parameter 8103
REFERENCE STEP 1.
8109 START FREQ 1
Sets the frequency limit used to start the first auxiliary motor. The first auxiliary motor starts if:
No auxiliary motors are running.
ACS550 output frequency exceeds the limit:
8109 + 1 Hz.
Output frequency stays above a relaxed limit
(8109 - 1 Hz) for at least the time: 8115
AUX MOT START D.
After the first auxiliary motor starts:
Output frequency decreases by the value =
(8109
START FREQ 1) - (8112 LOW FREQ 1).
In effect, the output of the speed regulated motor drops to
compensate for the input from the auxiliary motor.
See the figure, where:
A = (8109
START FREQ 1) - (8112 LOW FREQ 1)
B = Output frequency increase during the start delay.
C = Diagram showing auxiliary motor’s run status as frequency
increases (1 = On).
Note: 8109
START FREQ 1 value must be between:
8112
LOW FREQ 1
(2008
MAXIMUM FREQ) -1.
8110 START FREQ 2
Sets the frequency limit used to start the second auxiliary motor.
See 8109 START FREQ 1 for a complete description of the operation.
The second auxiliary motor starts if:
One auxiliary motor is running.
ACS550 output frequency exceeds the limit: 8110 + 1.
Output frequency stays above the relaxed limit (8110 - 1 Hz) for at least the time: 8115
AUX MOT START D.
8111 START FREQ 3
Sets the frequency limit used to start the third auxiliary motor.
See 8109
START FREQ 1 for a complete description of the operation.
The third auxiliary motor starts if:
Two auxiliary motors are running.
ACS550 output frequency exceeds the limit: 8111 + 1 Hz.
Output frequency stays above the relaxed limit (8111 - 1 Hz) for at least the time: 8115
AUX MOT START D.
Code Description
P 8115
(P 8109)+1
P 8112
A
B
1
0
C
P 8109
A
t
t
f (Hz)
f
MIN
f
MAX