FLN Protocol Technical Data
Detailed Point Descriptions
FLN Detailed Point Descriptions
Point Description
Drive
Parameter
1 CTRL ADDRESS The FLN address of the drive. It can be set by FLN and by
the panel.
5302
2 APPLICATION The Application ID for FLN on the ACH550. This ID is
assigned by Siemens for each unique application. It
correlates directly to a particular point list approved at the
time of release. Therefore, this point list shall remain fixed
once approval is granted. Any changes to the point list shall
require a new Application ID and re-approval by Siemens.
The Application ID assigned to ACH550 is 2934.
3 FREQ OUTPUT The output frequency applied to the motor, in Hertz. 0103
4 PCT OUTPUT The ratio of output frequency or speed to the corresponding
maximum rating, depending on control mode.
For scalar mode, it is the ratio of Output Frequency
(parameter 0103) to Maximum Frequency (parameter
2008).
For speed mode, it is the ratio Speed (parameter 0102) to
Maximum Speed (2002).
None. This
ratio is
calculated
by the FLN
application.
5 SPEED The calculated speed of the motor, in RPM. 0102
6 CURRENT The measured output current. 0104
7 TORQUE The calculated output torque of the motor as a percentage of
nominal torque.
0105
8 POWER The measured output power in KW. The FLN point definition
also supports horsepower by selecting English units.
0106
DRIVE TEMP The measured heatsink temperature, in
° C. The FLN point
definition also supports
° F by selecting English units.
0110
10 DRIVE KWH The drive's cumulative power consumption in kilowatt-hours.
This value may be reset by commanding FLN point 49,
RESET KWH.
0115
11 DRIVE MWH The drive's cumulative power consumption in megawatt
hours. This value cannot be reset.
0141
12 RUN TIME The drive's cumulative run time in hours. This value may be
reset by commanding FLN point 48, RESET RUN TIME.
0114
13 DC BUS VOLT The DC bus voltage level of the drive. 0107
14 OUTPUT VOLT The AC output voltage applied to the motor. 0109
15 PRC PID FBCK The Process PID feedback signal. 0130
16 PRC PID DEV The deviation of the Process PID output signal from its
setpoint.
0132
17 MOTOR TEMP The measured motor temperature as set up in Group 35. 0145
18 ROTATION CNT The motor's cumulative revolution count, in mega-
revolutions.
0142
19 N/A
20 OVRD TIME 1 of the 5 mandatory FLN points required for compatibility
with Siemens control systems. It has no functionality in the
drive application.
None