Activate Drive Control Functions – EFB
Miscellaneous Drive Control
Using the fieldbus for miscellaneous drive control requires:
Drive parameter values set as defined below.
Fieldbus controller supplied reference word(s) in the appropriate location. (The
location is defined by the Protocol Reference, which is protocol dependent.)
1. Use Memorize Point command.
Drive Parameter Value Setting
Protocol Reference
Modbus
N2 FLN
ABB DRV DCU PROFILE
1601 RUN
ENABLE
7 (COMM) Run enable by
fieldbus.
40001 bit 3 40031 bit 6
(inverted)
BO4 35
1604
FAULT
RESET SEL
8 (COMM) Fault reset by
fieldbus.
40001 bit 7 40031 bit 4 BO6 94
1606
LOCAL
LOCK
8 (COMM) Source for local
lock selection is the
fieldbus.
Does not
apply
40031 bit 14
1607
PARAM
SAVE
1 (SAVE) Saves altered
parameters to
memory (then value
returns to 0).
41607 40032 bit 2 BO18 N/A
1
1608 START
ENABLE 1
7 (
COMM) Source for start
enable 1 is the
fieldbus Command
word.
Does not
apply.
40032 bit 2
1609
START
ENABLE 2
7 (
COMM) Source for start
enable 2 is the
fieldbus Command
word.
40032 bit 3
2013
MIN
TORQUE
SEL
7 (COMM) Source for minimum
torque selection is
the fieldbus.
40031 bit 15
2014
MAX
TORQUE
SEL
7 (COMM) Source for
maximum torque
selection is the
fieldbus.
2201
ACC/DEC
1/2
SEL
7 (COMM) Source for ramp
pair selection is the
fieldbus.
40031 bit 10