Catalog | ABB industrial drives ACS880 single drives 21
Dimensions and weights of the du/dt filters
du/dt filter Height Width Depth Weight
mm mm mm kg
NOCH0016-60 195 140 115 2.4
NOCH0016-62/65 323 199 154 6
NOCH0030-60 215 165 130 4.7
NOCH0030-62/65 348 249 172 9
NOCH0070-60 261 180 150 9.5
NOCH0070-62/65 433 279 202 15.5
NOCH0120-60** 200 154 106 7
NOCH0120-62/65 765 308 256 45
NOCH0260-60** 383 185 111 12
FOCH0260-70 382 340 254 47
FOCH0320-50 662 319 293 65
FOCH0610-70 662 319 293 65
External du/dt filters for ACS880-01
ACS880 du/dt filter type (3 filters included in kits marked *)
Unprotected (IP00) Protected
to IP22
Protected
to IP54
NOCH0016-60
NOCH0030-60
NOCH0070-60
NOCH0120-60 *
)
NOCH0260-60 *
)
FOCH0260-70
FOCH0320-50
FOCH0610-70
NOCH0016-62
NOCH0030-62
NOCH0070-62
NOCH0120-62
NOCH0016-65
NOCH0030-65
NOCH0070-65
NOCH0120-65
400 V 500 V
02A4-3 02A1-5 1 1 1
03A3-3 03A0-5 1 1 1
04A0-3 03A4-5 1 1 1
05A6-3 04A8-5 1 1 1
07A2-3 05A2-5 1 1 1
09A4-3 07A6-5 1 1 1
12A6-3 11A0-5 1 1 1
017A-3 014A-5 1 1 1
021A-5 1 1 1
025A-3 027A-5 1 1 1
111
032A-3 034A-5 1 1 1
038A-3 040A-5 1 1 1
045A-3 052A-5 1 1 1
061A-3 065A-5 1 1 1
072A-3 077A-5 1 1 1
087A-3 096A-5 1 1 1
105A-3 124A-5 1 1 1
145A-3 156A-5 1
169A-3 180A-5 1
206A-3 240A-5 1
246A-3 2 60A-5 1
293A-3 1
363A-3 361A-5 1
430A-3 414A-5 1
** 3 filters included, dimensions apply for one filter.
Motor type Nominal AC supply voltage Requirements for
Motor insulation system
ABB du/dt and common mode filters,
insulated N-end motor bearings
P
N
< 100 kW and
frame size < IEC 315
100 kW ≤ P
N
< 350 kW or
IEC 315 ≤ frame size <
IEC 400
P
N
< 134 hp and
frame size < NEMA 500
134 hp ≤ P
N
< 469 hp or
NEMA 500 ≤ frame
size ≤ NEMA 580
Non-ABB motors
Random-
wound
and form-
wound
U
N
≤ 420 V
Standard
Û
LL
= 1300 V
-
+ N or CMF
420 V < U
N
≤ 500 V
Standard
Û
LL
= 1300 V
+ du/dt + du/dt + N or
+ du/dt + CMF
or
Reinforced:
Û
LL
= 1600 V, 0.2
microsecond rise time
-
+ N or CMF
500 V < U
N
≤ 600 V
Reinforced:
Û
LL
= 1600 V
+ du/dt + du/dt + N or
+ du/dt + CMF
or
Reinforced:
Û
LL
= 1800 V
-
+ N or CMF
600 V < U
N
≤ 690 V
Reinforced:
Û
LL
= 1800 V
+ du/dt + du/dt + N
Reinforced:
Û
LL
= 2000 V, 0.3
microsecond rise time
-
+ N or CMF
Abbr. Definition
U
N
Nominal AC line voltage.
Ü
LL
Peak line-to-line voltage at motor terminals which the motor insulation must withstand.
P
N
Motor nominal power.
du/dt
du/dt fi lter at the output of the drive. Available from ABB as an optional add-on kit.
CMF
Common mode fi lter. Available from ABB as an optional add-on kit.
N
N-ned bearing: insulated motor non-drive end bearing.
n.a.
Motors of this power range are not available as standard units. Consult the motor manufacturer.
The abbreviations used in the table are defined below